Frame 2 Installation

2-13

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Figure 2.12 Removing the Bottom Drive Cover

2. Remove the power section stirring fan.

a. Unfasten two bracket screws.
b. Disconnect the fan power leads (two fastons).

c. Lift the fan from the drive (

Figure 2.13

).

Figure 2.13 Removing the Power Section Stirring Fan

3. Depending on the supplied AC line voltage used to power the drive, see

Table 2.A

to determine which transformer tap to use.

Table 2.A Control Transformer Tap Usage

AC Line Voltage

Transformer Tap To Use

380V AC

400V

400V AC

440V AC

460V AC

480V

480V AC