Drive coolant requirements, Recommended coolants, Corrosion inhibitor – Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 98: Drive coolant requirements -10, Recommended coolants -10 corrosion inhibitor -10

Advertising
background image

4-10

Cooling Loop Installation

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P

Drive Coolant Requirements

Recommended Coolants

Table 4.B

lists approved sources and recommended coolants with

appropriate corrosion inhibitors

for the drive loop.

Table 4.B Recommended Drive Loop Coolants

Non-premixed coolants require a coolant-to-water mix ratio of 50% by
volume.

Important: Since coolant performance slowly degrades over time, we

recommend replacing the drive loop coolant every two years
and/or whenever the loop is drained for servicing.

Corrosion Inhibitor

If an approved coolant is not used, the drive coolant must consist of clean
water with a corrosion inhibitor. An approved corrosion inhibitor is
Chemtool, Inc. (www.chemtool.com) part number Watertool 4435-C. The
recommended concentration of the inhibitor is 8-10% by volume.
Deionized water is prohibited. Use distilled water or water with less than
50 ppm concentrations of these chemical compounds:

• Sulfate and chloride

• Hard water ions such as Mg++ and Ca++

Source

Coolant

Interstate Chemical

http://www.interstatechemical.com/

contact.htm

• NFP-50

(1)

; a 50/50 premix of propylene glycol and distilled water

• NFE-50

(1)

; a 50/50 premix of ethylene glycol and distilled water

Koolant Koolers/Dimplex Thermal
Solutions

http://www.koolantkoolers.com/

index.php/nic=contact

• K-Kool-E

(1)

; ethylene glycol (available premixed with distilled water)

• Propylene glycol

(1)

also available

Dow Chemical

http://www.dow.com

• Dowtherm

®

SR-1

(2)

; ethylene glycol

• Dowfrost

®

(2)

; propylene glycol

Dowtherm and Dowfrost are registered trademarks of the Dow Chemical Company

(1)

Available in 5 gallon pails.

(2)

Not premixed with distilled water, and may not be available in 5 gallon quantities.

!

ATTENTION: Ethylene and propylene glycols must be
inhibited and silicate free. Use of common silicate-containing,
automotive-type ethylene glycol solutions is prohibited as they
can damage the heat exchanger and/or drive and cooling
module equipment.