Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 118

Advertising
background image

A-2

Supplemental Drive Information

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P

Protection

(continued)

Logic Control Ride-Thru

Vector Control:

0.5 seconds minimum, 2 seconds typical

700S Phase II Control:

0.25 seconds, drive not running

Ground Fault Trip:

Phase-to-ground on drive output

Short Circuit Trip:

Phase-to-phase on drive output

Environment

Altitude:

1000 m (3280 ft) at rated current. See

Derating Guidelines on page A-4

for operation above 1000

m (3280 ft).

Maximum Surrounding Air
Temperature w/o Derating:

IP20, NEMA/UL Type 1:

0…50 °C (32…122 °F)

0…40 °C (32…104 °F)

Storage Temperature
(all constructions):

–40…85 °C (–40…185 °F)

Atmosphere:

Important: Drive must not be installed in an area where the ambient atmosphere contains
volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time,
it must be stored in an area where it will not be exposed to a corrosive atmosphere.

Relative Humidity:

5…95% non-condensing

Shock:

10G peak for 11 milliseconds duration (

± 1.0 ms)

Vibration:

0.152 mm (0.006 in.) displacement, 1G peak, 5.5 Hz

Sound:

Frame 2: Not available at time of publication.

Frame 3A: 78 dB

Frame 3B: 76 dB

Note: Sound pressure level is measured at 1 meter.

Electrical

Voltage Tolerance

Vector Control:

For full power and operating range, see the PowerFlex 700 Adjustable Frequency AC Drive—
Series B User Manual, publication 20B-UM002, Appendix C.

700S Phase II Control:

For full power and operating range, see the PowerFlex 700S High Performance AC Drive—Phase
II Control User Manual, publication 20D-UM006, Appendix C.

Input Frequency Tolerance:

27…93 Hz.

Input Phases:

Three-phase input provides full rating for all drives.

Displacement Power Factor:

0.98 across entire speed range.

Efficiency:

96.2% at rated amps, nominal line volts.

97.5% at rated amps, nominal line volts.

Maximum Short Circuit Current
Rating:

To match specified circuit breaker capability,

200,000 Amps

Actual Short Circuit Rating:

Determined by AIC rating of installed circuit breaker.

Motor Lead Lengths:

76 meters (250 feet) total

Control

Method:

Sine coded PWM with programmable carrier frequency.

Carrier Frequency:

2, 4, or 8 kHz. Drive rating based on 4 kHz.

Derating Guidelines on page A-4

for more

information.

2 or 4 kHz. Drive rating based on 4 kHz.

Output Voltage Range:

0 to rated motor voltage

Output Frequency Range

Vector Control:

0…420 Hz

700S Phase II Control:

0…350 Hz

Frequency Accuracy
(Vector Control only)

Digital Input:
Analog Input:

Within ± 0.01% of set output frequency.
Within ± 0.4% of maximum output frequency

Category

Specification

Frame 2

Frames 3A and 3B