3-2

Frame 3A and 3B Installation

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P

Figure 3.1 Frame 3 Complete Drive Installation Dimensions

Recommended Air Flow Clearances for Complete Drive

Verify that there is adequate clearance for air circulation around the drive
enclosures. A 15 cm (6 in.) minimum clearance is required wherever vents
in the cabinet are located.

Dimensions are in

millimeters and (inches).

C

G

H

J

D Max.

F Max.

E

B

A

INPUT

FILTER BAY

POWER

MODULE BAY

61 (2.39)

65 (2.56)

38

(1.50)

Ш35 (Ш1.38)

OUTLET

INLET

Frame
Size

Dimensions mm (in.)

Approximate Weight
of Complete Drive

A

B

C

D

E

F

G

H

J

3A

1200
(47.2)

2000
(78.7)

600
(23.6)

2078
(81.9)

1500
(59.1)

233
(9.2)

542
(21.3)

542
(21.3)

535
(21.1)

950 kg (2090 lb)

3B

1600
(63.0)

2200
(86.6)

800
(31.5)

2278
(89.8)

1500
(59.1)

233
(9.2)

542
(21.3)

942
(37.1)

735
(28.9)

1361 kg (3000 lb)