Recommended air flow clearances for complete drive – Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 50

3-2
Frame 3A and 3B Installation
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P
Figure 3.1 Frame 3 Complete Drive Installation Dimensions
Recommended Air Flow Clearances for Complete Drive
Verify that there is adequate clearance for air circulation around the drive
enclosures. A 15 cm (6 in.) minimum clearance is required wherever vents
in the cabinet are located.
Dimensions are in
millimeters and (inches).
C
G
H
J
D Max.
F Max.
E
B
A
INPUT
FILTER BAY
POWER
MODULE BAY
61 (2.39)
65 (2.56)
38
(1.50)
Ш35 (Ш1.38)
OUTLET
INLET
Frame
Size
Dimensions mm (in.)
Approximate Weight
of Complete Drive
A
B
C
D
E
F
G
H
J
3A
1200
(47.2)
2000
(78.7)
600
(23.6)
2078
(81.9)
1500
(59.1)
233
(9.2)
542
(21.3)
542
(21.3)
535
(21.1)
950 kg (2090 lb)
3B
1600
(63.0)
2200
(86.6)
800
(31.5)
2278
(89.8)
1500
(59.1)
233
(9.2)
542
(21.3)
942
(37.1)
735
(28.9)
1361 kg (3000 lb)