Frame 3A and 3B Installation

3-35

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Figure 3.32 Frame 3A 700S Phase II Control Synchronization Cable Connection

Inverter-to-Converter DPI Communication Cable

To enable the Inverter and Converter section of the Frame 3A Power
Module to communicate with each other, a factory-installed DPI
communication cable is used. No user connection is required.

Synchronization
Connections for Frame 3B

Coupled or Stand-Alone Inverter Power Modules

Frame 3B Inverter Power Modules may be configured in two ways. One
way is an Inverter Power Module coupled with a Converter Power Module.
The coupling is achieved by using two cables: a control synchronization
cable and an inverter-to-converter DPI connection cable. The other way is a
stand-alone Inverter Power Module. In this case, synchronization and DPI
connection cables are not needed to connect the Inverter Power Module to
the Converter Power Module. The two cables for coupling are described in
the next two subsections.

P6 Header on

700S Phase II

Control Cassette

Control Synchronization

Cable (Factory-Installed)

J9 Header on

Active Converter

Control Cassette

24 VDC

DC POSITIVE

DC NEGATIVE

1 120 VAC

2 PRECHARGE COIL

6 INDUCTOR OVERTEMP

WIRE RANGE:
24-10 AWG
(0.2-4 MM)

4 CHARGE FEEDBACK

GATE ENABLE

STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)