Carrier frequency, Horsepower/current ratings – Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 121

Advertising
background image

Supplemental Drive Information

A-5

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Carrier Frequency

For Frame 2 drives, see the carrier frequency derating table below.
PowerFlex 700L Frame 3A and 3B drives cannot be run above 4 kHz.

Horsepower/Current
Ratings

The following tables provide normal duty and heavy duty drive ratings
(including continuous, 1 minute, and 3 second).

Table A.A 400V AC Ratings (AC Input/AC Output)

Table A.B 480V AC Ratings (AC Input/AC Output)

Table A.C 600V AC Ratings (AC Input/AC Output)

2

0

4

6

8

360

Output

(Amps)

293 Amps
(80%)

Carrier Frequency (kHz)

Drive
Catalog
Number

Fra

m

e

PWM
Freq.
(kHz)

Output Power

Output Current (with 400V AC Induction Motor)

(1)

HP (kW)

Cont.

110%
1 min.

150%
3 secs.

Cont.

150%
1 min.

200%
3 secs.

ND

HD

ND

ND

ND

HD

HD

HD

20LC360

2

4

268 (200)

200 (150)

360

396

540

264

396

540

20LC650

3A

4

500 (370)

365 (270)

650

715

975

475

715

975

20LC1K2

3B

4

960 (715)

700 (525)

1250

1375

1875

915

1375

1875

(1)

Frame 2 ratings are based on 50 °C ambient and 50 °C coolant.
Frame 3A and 3B ratings are based on 40 °C ambient and 40 °C coolant.

Drive
Catalog
Number

Frame

PWM
Freq.
(kHz)

Output Power

Output Current (with 480V AC Induction Motor)

(1)

HP (kW)

Cont.

110%
1 min.

150%
3 secs.

Cont.

150%
1 min.

200%
3 secs.

ND

HD

ND

ND

ND

HD

HD

HD

20LD360

2

4

300 (224)

235 (175)

360

396

540

264

396

540

20LD650

3A

4

600 (445)

440 (325)

650

715

975

475

715

975

20LD1K2

3B

4

1150 (860)

845 (630)

1250

1375

1875

915

1375

1875

(1)

Frame 2 ratings are based on 50 °C ambient and 50 °C coolant.
Frame 3A and 3B ratings are based on 40 °C ambient and 40 °C coolant.

Drive
Catalog
Number

Fra

m

e

PWM
Freq.
(kHz)

Output Power

Output Current (with 600V AC Induction Motor)

(1)

HP (kW)

Cont.

110%
1 min.

150%
3 secs.

Cont.

150%
1 min.

200%
3 secs.

ND

HD

ND

ND

ND

HD

HD

HD

20LE425

3A

4

465 (345)

345 (255)

425

470

640

315

470

640

20LE800

3B

4

870 (650)

640 (480)

800

885

1200

590

885

1200

20LE1K1

3B

2

(2)

1275 (955)

935 (695)

1175

1295

1765

860

1295

1765

(1)

Frame 3A and 3B ratings are based on 40 °C ambient and 40 °C coolant.

(2)

Must operate at only 2 kHz PWM, and only as a stand-alone inverter module (“K” in catalog string position 13).

Advertising