Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 79

Advertising
background image

Frame 3A and 3B Installation

3-31

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Table 3.D Power Module Control Wiring Terminal Specifications

Wire the Input Filter Bay to the Power Module Bay in accordance with

Table 3.E

and drive schematics in

Appendix C

.

Table 3.E Input Filter-to-Power Module Bay Wiring

Item Name

Description

Wire Size Range

(1)

Recommended
Tightening
Torque (+10%)

Wire Strip
Length

Wire
Terminal

Maximum

Minimum

400/480V Line Voltage
Fuses FU7, FU8, and FU9

Input filter AC power

21.1 mm

2

(#4 AWG)

2.1 mm

2

(#14 AWG)

4 N

•m

(35 lb

•in)

(2)

(2)

600/690V Line Voltage
Fuses FU7, FU8, and FU9

21.1 mm

2

(#4 AWG)

2.1 mm

2

(#14 AWG)

4 N

•m

(35 lb

•in)

6 mm
(0.25 in.)

not
applicable

Terminal Blocks—TB2

Input filter control signals

3.3 mm

2

(#12 AWG)

0.3 mm

2

(#22 AWG)

1.5 N

•m

(13 lb

•in)

13 mm
(0.51 in.)

not
applicable

Active Converter Cassette
Terminal Blocks—P1 and P2

Active Converter AC power and
control wiring

3.3 mm

2

(#12 AWG)

0.3 mm

2

(#22 AWG)

0.8 N

•m

(7 lb

•in)

8 mm
(0.31 in.)

not
applicable

SHLD Terminal

Terminating point for control
wiring shields on Power Module

2.1 mm

2

(#14 AWG)

0.3 mm

2

(#22 AWG)

1.4 N

•m

(12 lb

•in)

10 mm
(0.39 in.)

not
applicable

Terminal Blocks—TB5 and
TB6

Power Module control wiring

4.0 mm

2

(#10 AWG)

0.2 mm

2

(#24 AWG)

1.4 N

•m

(12 lb

•in)

8 mm
(0.31 in.)

not
applicable

Fan—M6

Power Module Bay cooling fan

4.0 mm

2

(#10 AWG)

0.3 mm

2

(#22 AWG)

0.8 N

•m

(7 lb

•in)

8 mm
(0.31 in.)

not
applicable

(1)

Maximum/minimum sizes that the terminals will accept - these are not recommendations.

(2)

For 400/480V applications, terminate wires with #10 spade tongue terminal. Maximum terminal width is 11 mm (0.43 in.). Wire strip length per terminal
manufacture’s recommendation.

From

To

Comments

FU7

PMC P2-1

PMC = Power Module, Converter

FU8

PMC P2-4

FU9

PMC P2-7

TB2-1

PMC P1-9

TB2-1

PMC TB5-1

TB2-3

M6-N

M6 = Power Module Bay Door Fan

TB2-4

PMC TB5-3

TB2-5

PMC P1-10

TB2-6

PMC TB5-2

TB2-6

M6-L1

TB2-7

M6-PE

TB2-9

PMC TB5-4

TB2-10

PMC TB5-7

TB2-11

PMC TB5-5

PMC TB5-4

PMC TB5-6

Factory-installed jumper

Advertising