Frame 3A and 3B Installation

3-25

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Table 3.B Frame 3 Power Terminal Specifications

Installing an External/Separate Input Disconnect

An input disconnect can be installed in the line before the drive input
terminals in accordance with local, national, and international codes (for
example, NEC/CEC). Size the disconnect according to the in-rush current
as well as any additional loads the disconnect might supply. Coordinate the
trip rating for the inrush current (10-12 times full load current) with that of
the input isolation transformer, if used. See

Installing Transformers and

Reactors (Not Recommended) on page 3-23

for additional information.

Installing Power Wiring from Input Filter Bay to the Power Module Bay

Use the following steps to connect AC input power to the drive.

1. Connect the three-phase AC input power leads (three-wire 380-480V

AC or three-wire 600-690V AC, depending on drive nameplate voltage
rating) to the R/L1, S/L2, and T/L3 input power terminals on the drive:

Frame 3A Combined Converter/Inverter Power Module (for terminal

locations, see

Figure 3.2

,

Figure 3.18

, and

Figure 3.25

).

Frame 3A Dual Inverter Power Module (for terminal locations, see

Figure 3.2

,

Figure 3.18

, and

Figure 3.26

).

Frame 3B Separate Converter Power Module (for terminal locations,

see

Figure 3.3

,

Figure 3.21

, and

Figure 3.27

).

2. Tighten the AC input power terminal connections to the recommended

torque as shown in

Table 3.C

.

Item Name

Description

Frame
Size

Wire Size Range

(1)

Recommended Tightening
Torque (+10%)

Maximum

Minimum

Input Power Wire Lugs
R/L1, S/L2, T/L3

Input power
connections on drive

3A

400 MCM

3/0

42 N

•m (375 lb•in)

3B

1000 MCM

500 MCM

62 N

•m (550 lb•in)

PE Wire Lug

Terminating point for
ground wires

3A or
3B

600 MCM

#2 AWG

34 N

•m (300 lb•in)

(1)

Maximum/minimum sizes that the terminals will accept - these are not recommendations.

!

ATTENTION: Do not route signal and control wiring with
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution can result
in damage to, or destruction of, the equipment.