Frame 3A and 3B Installation

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P

Depending on the supplied AC line voltage used to power the drive, connect
FU1 and FU2 to TB1 in accordance with

Table 3.A

. See

Figure 3.29

or

Figure 3.30

for fuse and terminal block locations.

Table 3.A Input Voltage Setting for Control Transformer

Figure 3.23 Frame 3A Regenerative Drive Input Power and PE Wiring

Figure 3.24 Frame 3B Regenerative Drive Input Power and PE Wiring

Supplied Input Voltage

From

To

For all input voltages

FU1

TB1-1

380/415V AC

FU2

TB1-2

440/480V AC

FU2

TB1-3

575/600V AC

FU2

TB1-4

690V AC

FU2

TB1-5

L1 L2 L3

PE

INPUT FILTER BAY

DETAIL

L1

PE

L2

L3

INPUT FILTER BAY

DETAIL

L1

PE

L2

L3

L1

PE

L2

L3