Cooling Loop Installation

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P

Chiller

The chiller uses refrigerant to transfer heat from a liquid to air. This is a
simple closed loop system—it does not require a water supply from the
user. A chiller can achieve almost any coolant temperature required.
Coolant temperature should be at or above ambient temperature to avoid
condensation on drive components.

Figure 4.5 Drive and Chiller Plumbing Arrangement

Figure 4.6

shows a cooling loop diagram for a typical chiller.

Figure 4.6 Chiller Plumbing Diagram

PowerFlex 700L

Drive

Inlet

Flow

Indicator

Drive

Outlet

Hose Kit

= hose or pipe connection

To

Drive

Inlet

Radiator

From

Drive

Outlet

Chiller

Drive

Out

In

Reservoir

Pump

Condenser/Subcooler

Fan

Compressor

SOL

LS

TE

FS

TE

Ambient

Sensor

Sight Glass

Thermostatic

Expansion Valve

Filter-Drier

Drive Coolant

Temperature

Flow

Switch

Level

Switch