Control enable – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 112

Advertising
background image

8-4

Communications

1560E-UM050B-EN-P - June 2013

Connecting the Human Interface Module to the Controller

Figure 8.1 shows the connection of the SMC-Flex controller to a human
interface module. Table 8.C provides a description of each port.

See Figure 1.24 or 1.27 for the control wiring diagram that enables start-stop
control from a human interface module.

Port 5 – DPI Communications

Port 2

Ports 2 and 3 when two HIMs

are connected with a splitter

Port 5 – DPI Communications

Port 2

Ports 2 and 3 when two HIMs

are connected with a splitter

Figure 8.1 – SMC-Flex Controller with Human Interface Module

Table 8.C – Description of Ports

Port #

Description

1

Unused – Not available for use

2

First 20-HIM connected to SMC-Flex

3

Second 20-HIM connected to SMC-Flex

5

DPI Communication Board port

Control Enable

To enable motor control from a connected human interface module, follow
the procedure below with the connected human interface module’s
programming keys.

The Bulletin 20-HIM-LCD human interface modules with control panels
can start and stop the SMC-FLEX controller. However, the factory default
settings disable control commands other than Stop through the serial
communication port.

To enable motor control from a connected human interface module or
communication module, you must take the following programming steps: