9-4

Troubleshooting

% 5-" %. 0

Table 9.A – Fault Display Explanation (cont.)

Display

Fault Code

Possible Causes

Possible Solutions

Phase Reversal

26

• Incoming supply voltage is not in

the expected ABC sequence

• Check power wiring
• Disable protection if not needed

Comm Loss

27, 28, 29

• Communication disconnection at

the serial port

• Check for a communication cable disconnection to the

SMC-Flex controller

Network

30, 31, 32

• DPI network loss

• Reconnect for each DPI connected device

Ground Fault

33

• Ground fault current level has

exceeded programmed values

• Check power system and motor; correct if necessary
• Check programmed ground fault levels to match

application requirements

Excess Starts/Hr.

34

• Number of starts in a one-hour

period has exceeded the value
programmed

• Wait an appropriate amount of time to restart
• Consult factory if more than 2 starts per hour are

required

Power Loss

:

(with phase indication)

35, 36, 37

• Missing supply phase (as indicated)
• Loss of feedback

• Check for open line (i.e., blown line fuse)
• Check CT connections, replace Interface board

Hall ID

38

• Faulty interface

• Check ribbon cable connections between interface

board and control module

• Replace interface board

NVS Error

39

• Data entry error

• Check user data and perform a User Store function
• Replace control module

System Faults

128 to 209

• Control module internal fault

• Cycle control power to reset the control module
• If fault persists, replace control module

: Prestart fault indication

Table 9.B – Motor Will Not Start – No Output Voltage to the Motor

Display

Possible Causes

Possible Solutions

Fault displayed

• See fault description

• See Table 9.A addressing fault conditions

Display is blank

• Control voltage is absent
• Failed control module

• Check control wiring and correct if necessary
• Replace control module

Stopped
0.0 Amps

• Pilot devices
• SMC Enable input is open at

terminal 13

• Terminal 16 is open
• Start-Stop control has not been

enabled for the human interface
module

• Control voltage
• Failed control module

• Check wiring
• Check wiring

• Check wiring
• Follow the instructions on page 2-16 to 2-18

to enable control capability

• Check control voltage
• Replace control module

Starting

• Two or three power phases are

missing

• Check power system
• Check voltage sensing module and connections

Table 9.C – Motor Rotates (but does not accelerate to full speed)

Display

Possible Causes

Possible Solutions

Fault displayed

• See fault description

• See Table 9.A addressing fault conditions

Starting

• Mechanical problems

• Inadequate Current Limit setting
• Failed control module

• Check for binding or external loading and correct
• Check motor
• Adjust the Current Limit Level to a higher setting
• Replace control module