Basic setup (cont.) – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 92

Advertising
background image

4-12

Programming

1560E-UM050B-EN-P - June 2013

Parameter

Option

Current Limit Level v

The current limit level that is applied for the Ramp

time selected.

50 to 600% FLC

Kickstart Time

A boost current is provided to the motor for the

programmed time period.

0.0 to 2.0 s

Kickstart Level

Adjusts the amount of current applied to the motor

during kickstart.

0 to 90% of locked rotor

torque

Option 2 Input

Allows the user to select a Dual Ramp or Preset

Slow Speed (SS).

Disable, Preset SS,

Dual Ramp

Emergency Run x

Stop Mode

Allows the user to program the SMC-Flex controller

for the type of stopping that best fits the application.

Disable, Soft Stop,

Linear Speed

Stop Time

This sets the time period which the controller will

ramp the voltage during a stopping maneuver.

0.0 to 120 s

CT Ratio

Scales the CT input to actual motor current

(5 amp secondary assumed)

1 to 1500

Aux1 Config

N.O. contact is provided as standard with the

SMC-Flex controller. This contact is located at

terminals 19 and 20. Aux Contacts 1 allows the

user to configure the operation of the contacts.

Normal, Up-to-speed/Bypass

Fault Contact

A fault auxiliary contact is provided between terminals

29 and 30. Fault Contact allows the user to program

the operation of the contact for a fault condition.

N.O., N.C.

Alarm Contact

An alarm contact is provided between terminals 31

and 32. Alarm contact allows the user to program

the operation of the contact for an Alarm condition.

N.O., N.C.

Aux2 Config

This parameter provides the user with the ability to

program the “Normal” state of the second auxiliary

contact. This contact is located at terminals 33 and 34.

N.O., N.C.

Parameter Mgmt w

The newly programmed parameters’ values can be

saved to memory, or the factory default parameter

values can be recalled.

Ready, User Store, User

Recall, Load Default

v

Starting Mode must be programmed to Current Limit to obtain access to the Current Limit Level

parameter.

w

The new programmed parameter values will not be stored to the EEPROM without the user’s

direction in Parameter Management: User Store.

x

When programmed for ‘Emergency Run’ and the Option 2 input is energized, a ‘Start’ command

will first close the bypass contactor, then the line contactor for an across-the-line start of the motor.

A ‘Stop’ command will open the line contactor first and allow the motor to coast, regardless of the

programmed ‘Stop Mode’. For Pump Option modules, the Option 2 input defaults to ‘Emergency

Run’ for MV applications.

Basic Setup (cont.)