Chapter 6 - options, Overview, Human interface module – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 99: Options, Chapter

Advertising
background image

Options

Overview

The SMC-Flex controller offers a variety of unique control programming
and communication options that provide enhanced capabilities. (See
Chapter 1 for brief descriptions of each option.)

Note: Only one option can reside in a controller.

Human Interface Module

The control buttons available with the Bulletin 20-HIM Human interface
modules are compatible with the SMC-Flex controller’s control options.
The following table details the functionality of each button with regards to
each option.

Notes: (1) The logic mask port must be enabled prior to initiating control

commands to the SMC-Flex controller. Refer to Control
Enable
on page 2-16 for instructions.

(2) The control terminals must be wired according to

Figure 3.10 on page 3-10 and Figure 3.16 on page 3-16.

Option

Action

Operation

Standard

II

The green start button, when pressed, will

commence motor acceleration to full speed.

O

O

The red stop button, when pressed, will

provide a coast stop, and/or reset a fault.

Soft Stop

Current Limit

Full Voltage

Linear Speed

Jog

Jog

The jog button, when pressed, will initiate the

programmed maneuver.

II

The green start button, when pressed, will

commence motor acceleration to full speed.

O

O

The red stop button, when pressed, will

provide a coast stop.

Preset

Slow Speed

Jog

Jog

The jog button is not active for Preset Slow

Speed.

* Slow Speed cannot be operated via the

HIM.