Parameter Modification

All parameters are modified using the same method. The basic steps to
performing parameter modification are described below.

Note:

Parameter values modified while the motor is operating are not
valid until the next start sequence begins.

Description

Action

Display v

1. Press the ESC key to go from the

status display to the Main menu.

Esc

Esc

2. Scroll with the Up/Down keys until

the Preferences option is

highlighted.

3. Press the Enter key to access the

Parameter menu.

4. Scroll with the Up/Down keys

until the option you want to use

(Monitoring, Motor Protection,

etc.) is highlighted. For this

example, Set Up will be used.

5. Press Enter to select the Set Up

group.

6. Scroll to Basic Set Up and press

Enter. u

7. Scroll to the Starting Mode

parameter by using the Up/Down

keys, and press Enter.

8. Press Enter to select the option.

Scroll to the option of your choice

by using the Up/Down keys. For

this example, we will choose

Current Limit.

9. Press the Enter key to accept the

new setting.

10. Scroll to the next parameter by

using the Down key. Continue

the process until all desired

settings are entered.

11. To save modifications to memory,

scroll to Parameter Mgmt, press

Enter twice and scroll to User

Store. Press the Enter key again

to save the new settings to

EEPROM.

u

The SMC Option advises the user if any control option (i.e., Pump Control) is resident. This parameter is

factory set and cannot be modified by the user.

v

The display will indicate that the second line is now active by highlighting the first character. If the LCD

display does not provide a highlighted cursor, then the controller is in the Display mode.