Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 172

Advertising
background image

A-8

Specifications

1560E-UM050B-EN-P - June 2013

Table A.8 – Control Wire and Power Wire

Description

Specifications

Control Wire
All Medium Voltage structures shall be equipped with control wire which meets the following specifications:

Type

TEW, Stranded Copper Wire

(Tinned)

AWG Size (Control Circuit)

#14 AWG – 1.5 mm

2

AWG Size (Current Transformer Circuit)

#12 AWG – 2.5 mm

2

Number of Strands

19

Maximum Voltage Rating

600 V

Maximum Rated Temperature

105°C (221°F)

Terminal Blocks

1492-CA1, -CA3

Power Wire
Power wire used to feed the primary of the control power transformer or potential transformers is as follows :
AWG Size

#8 AWG

Type

Alcatel Excelene XLPE MV90

Insulation Rating Ê

5.0 kV

Maximum Temperature Rating

90°C (194°F)


The controller shall be wired with the following non-shielded, stranded wire type, based on the current ratings :

Controller

Rating (Amps)

AWG Size

Type

Insulation

Rating Ë

Maximum Temperature

Rating

200

#2

EP-CSPE MV90

8.0 kV

90°C (194°F)

400

#4/0

EP-CSPE MV90

8.0 kV

90°C (194°F)

600

(2) x #4/0

EP-CSPE MV90

8.0 kV

90°C (194°F)

Ê

For 7.2 kV rated controllers, #8 AWG — 8.0 kV EP-CSPE MV90, non-shielded stranded cable is used.

Ë

For 7.2 kV rated controllers, #2 AWG, #4/0 AWG, or 350 kcmil MCM – 8.0 kV EP-CSPE MV90, non-shielded

stranded cable is used.

Advertising