Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 171

Advertising
background image

Specifications

A-7

1560E-UM050B-EN-P - June 2013

Table A.7 – Power Fuses and Losses

Description

Specifications

Power Fuses and Fuse Holders
This section details the power fuse and fuse holder technical information that each medium voltage product

conforms to. It includes information on R-rated fuses, as well as mounting dimensions.
Fuse Types
R Rated :

2R to 24R

2R to 24R

19R, 38R

Interrupting Ratings : 2.4 kV to 7.2 kV

A480R – 5.0/2.4 kV

A072 – 7.2 kV

A051B – 5.0/2.4 kV

50 kA RMS SYM (80 kA RMS ASYM)

Mounting (Center) Dimensions

Clip-On

304.8 mm (12.0 in)

Bolt-On

454.2 mm (17.88 in)

Maximum Heat Dissipation (kW) (Convection)

Start or Stop Cycle

(@ 450% Starting Duty)

180 A 360 A 600 A

Continuous

2500 V

13.5

19.2

45.3

.250

5000 V

27.0

38.5

90.5

.250

Controller Rating

7200 V

40.5

57.7

136.0

.250

Power Losses

Current (A)

Fuse Size

Losses (kW)

± 10%

90

6R

.125

180

12R

.350

240

18R

.510

360

24R

1.000

Power Cell Losses

600

57X

1.500

Bus Rating (A)

Fully Loaded Bus

Losses per 915 mm (36 in.)

Section

(Watts) ±%

1200

150

2000

200

Power Bus Losses

3000

200

Control Power Transformer Losses

The losses from a 500 VA control power transformer fully

loaded are approximately 50 W per controller.

Low Voltage Panel Losses

The losses from the standard control circuit

are approximately 25 W per controller.