Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual
Page 175

Parameter Information
B-3
1560E-UM050B-EN-P - June 2013
Table B.1 – Parameter List (cont.)
Group
Parameter Description
Parameter
Number
Units
Min / Max
Default
Settings
User
Settings
Gnd Flt Enable
72
Disable
Enable
Disable
Gnd Flt Level
73
A
1.0…5.0
2.5
Gnd Flt Delay
74
SEC
0.1…250.0
0.5
Gnd Flt Inh Time
75
SEC
2.25
10
Gnd Flt A Enable
76
Disable
Enable
Disable
Gnd Flt A Lvl
77
A
1.0…5.0
2.0
Ground Fault
Gnd Flt A Dly
78
SEC
0…250
10
PTC
PTC Enable
79
Disable
Enable
Disable
Phase Reversal
Phase Reversal
80
Disable
Enable
Disable
Starts Per Hour
81
0…99
2
Restart Attempts
82
0…5
2
Restart
Restart Delay
83
SEC
0…60
0
Comm Masks
Logic Mask
87
8-bit binary
Data In A1
88
Data In A2
89
Data In B1
90
Data In B2
91
Data In C1
92
Data In C2
93
Data In D1
94
Data In D2
95
Data Out A1
96
Data Out A2
97
Data Out B1
98
Data Out B2
99
Data Out C1
100
Data Out C2
101
Data Out D1
102
Data Links
Data Out D2
103
Motor Data
Motor ID
104
0…65535
0