Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 168

Advertising
background image

A-4

Specifications

1560E-UM050B-EN-P - June 2013

Table A.4 – Cable Quantity and Size

Bulletin

Size

Structure

Code

Unit Size

Inches (mm)

Max. No. & Size of

Incoming cables-no bus

Max. No. & Size of

Incoming Cables-w/bus

Max. No. & Size of

Exiting Load Cables

1560E

200/400A

14.60

26 W X 91 H

(660 X 2311)

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 250mcm/phase

1560E

200/400A

14.62

36 W X 91 H

(914 X 2311)

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 350mcm/phase

1560E

600A

14.64

44 W X 91 H

(1118 X 2311)

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 350mcm/phase

1562E

200/400A

14.70

36 W X 91 H

(914 X 2311)

(1) 500/

(2) 250mcm/phase

(1) 750/

(2) 500mcm/phase

(1) 500/

(2) 350mcm/phase

1562E

200/400A

14.72

62 W X 91 H

(1575 X 2311)

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 250mcm/phase

(1) 500/

(2) 250mcm/phase

1562E

600A

14.74

80 W X 91 H

(2032 X 2311)

(1) 750mcm/phase

(1) 750/

(2) 500mcm/phase

(1) 500/

(2) 350mcm/phase

1562E

600A

14.76

100 W X 91 H

(2540 X 2311)

(1) 750mcm/phase

(1) 750/

(2) 500mcm/phase

(1) 1000/ (2) 750/

(4) 500mcm/phase

Notes:
1.

Restrictions based upon single conductor cable.

2.

Please contact factory for multiple conductors, shielded, or other specialized cables.

3.

Please contact factory if the maximum number/size needs to be exceeded. We can accommodate special requests by

incorporating landing pads (if room is available) or cable terminating units.

4.

The customer is responsible to size the cables and conduits in accordance with applicable installation codes.