Appendix a - specifications, Appendix – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 165

Advertising
background image

Appendix

A

1560E/1562E SMC-Flex Specifications

1560E-UM050B-EN-P - June 2013

Table A.1 – Specifications
Electrical Ratings

UL/CSA/NEMA

IEC

Power Circuit
Method of Connection

Motor in delta or star; SCRs between windings and supply

Number of Poles

Equipment designed for three phase loads only

Rated Voltage (Ur)

2400 V AC (-15%, +10%)

3300 V AC (-15%, +10%)

4200 V AC (-15%, +10%)

6900 V AC (-15%, +10%)

3.6 kV

7.2 kV

Rated Insulation Voltage (Ui)

2500 V

5000 V

7200 V

3.6 kV

7.2 kV

Rated Impulse Voltage (Uimp)

60 kV

(3.6 kV) 40 kV

(7.2 kV) 60 kV

Dielectric Withstand

(2500 V) 7,625 V AC

(5000 V) 13,250 V AC

(7200 V) 18,200 V AC

(3.6 kV) 10 kV

(7.2 kV) 20 kV

Repetitive Peak Inverse Voltage Rating

2500 V max. 6,500 V (2 SCRs per phase)

5000 V max. 13,000 V (4 SCRs per phase)

7200 V max. 19,500 V (6 SCRs per phase)

Output Rating

100 to 7500 hp

75 to 5600 kW

Semi-Conductor Isolation

Fiber optic

Operating Frequency

50/60 Hz

50/60 Hz

dv/dt Protection

RC Snubber Network

Transient Protection

Integrated overvoltage trigger circuit

Rated Current

180 A

360 A

600 A

dv/dt

180 A

1000 V/µs

360/600 A

2000 V/µs

di/dt

180/360/600 A

200 A/µs

Voltage Drop

(Line to Output Terminals)

2.5 V per SCR without bypass;

Less than 1.0 V with bypass, total

Overall Efficiency

99.95% with bypass

Starting Torque

0 to 90% of motor torque

Thermal Capacity

600%, 10 seconds

450%, 30 seconds

Ramp Time

0 to 30 seconds

(Consult Factory for Longer Time)

Acceleration Kick

550% for 0.0 to 2.0 seconds

Approvals

UL E102991
CSA LR12235 (pending)

Safety : 92/59/EEC (Directive)

TI/061/1198 (Certificate)

Ref : BSEN 61010-1 :1993

BSEN 60204-1 :1997

EMC : 89/336/EEC, 92/31/EEC,

93/68/EEC (Directives)

T703ALB1 (Certificate)

Ref : EN 61000-6.4 :2001

EN 61000-6.2 :2001

Advertising