Motor Information

The Basic Set Up and Overload programming group allows the user to set
parameters indicating to the controller which motor is connected. It is
important to correctly input the data to achieve the best performance from
your controller.

For overload protection, it is critical that the data be
entered as it appears on the motor nameplate.

Motor Data Entry

In the Program mode, enter the correct values into the Overload group:

Description

Option

Display

Overload Class vw
The factor default setting disables

overload protection. To enable it, enter

the desired trip class in this parameter.

Disable, 10, 15, 20,

30

Service Factor vw
Enter the value from the motor’s

nameplate.

0.01 to 1.99

Motor FLC uvw
Enter the value from the motor’s

nameplate.

1.0 to 1000A

Overload Reset vw
Allows the user to select either a manual

or auto reset after an overload.

Manual, Auto

Motor Connection w
Enter the type of motor being connected

to the SMC-Flex: Line or Delta

Line, Delta

Line Voltage uw
Enter the system voltage in this

parameter. This must be done to ensure

optimum motor performance and correct

operation of undervoltage and

overvoltage protection.

1 to 10,000 V

u

Refer to the SMC -Flex controller nameplate for maximum ratings. Exceeding these could result in

damage to the controller.

v

Found in Overload programming group. Only one location needs to be programmed.

w

Found in Basic Set Up programming group.

A T T E N T I O N

A T T E N T I O N