Emc compliance, Enclosure, Wiring – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 66

Advertising
background image

2-18

Installation



% 5-" %. 0

This product has been designed for Class A equipment.
Use of the product in domestic environments may cause
radio interference, in which case, the installer may need
to employ additional mitigation methods.

The following guidelines are provided for EMC installation compliance.

Enclosure

Install the product in a grounded metal enclosure.

Wiring

Wire in an industrial control application can be divided into three groups:
power, control, and signal. The following recommendations for physical
separation between these groups is provided to reduce the coupling effect.

• Different wire groups should cross at 90° inside an enclosure.

• Minimum spacing between different wire groups in the same tray should

be 16 cm (6 in.).

• Wire runs outside an enclosure should be run in conduit or have

shielding/armor with equivalent attenuation.

• Different wire groups should be run in separate conduits.

• Minimum spacing between conduits containing different wire groups

should be 8 cm (3 in.).

• For additional guidelines, please refer to Wiring and Ground guidelines,

publication DRIVES-IN001A-EN-P.

• Wire earth ground to control terminal 14.

• Use shielded wire for:

PTC Input
Tach Input
Ground Fault Input

• Terminate shielded wires to terminal 14.

• Ground fault CT must be inside or within 3 m of metal enclosure.

A T T E N T I O N

A T T E N T I O N

EMC Compliance