Programming

4-9

1560E-UM050B-EN-P - June 2013

Soft Start

The following parameters are specifically used to adjust the voltage ramp
supplied to the motor.

Parameter

Option

Starting Mode

This must be programmed for Soft Start.

Soft Start

Ramp Time

u

This programs the time period that the controller

will ramp the output voltage up to full voltage from

the initial Torque level programmed.

0 to 30 s

Initial Torque

The initial reduced output voltage level for the

voltage ramp to the motor is established and

adjusted with this parameter.

0 to 90% locked rotor torque

Kickstart Time

A boost of current is provided to the motor for the

programmed time period.

0.0 to 2.0 s

Kickstart Level

Adjusts the amount of current applied to the motor

during the kickstart time.

0 to 90/% locked rotor torque

u

If the controller senses that the motor has reached full speed before completing the Soft Start, it

will automatically switch to providing full voltage to the motor.

Current Limit Start

To apply a fixed, reduced-output voltage to the motor, the following
parameters are provided for user adjustment:

Parameter

Option

Starting Mode

This must be programmed for Current Limit.

Current Limit

Ramp Time

u

This programs the time period that the controller

will hold the fixed, reduced output voltage before

switching to full voltage.

0 to 30 s

Current Limit Level

This parameter provides adjustability for the

reduced output voltage level provided to the motor.

50 to 600% full load current

Kickstart Time

A boost of current is provided to the motor for the

programmed time period.

0.0 to 2.0 s

Kickstart Level

Adjusts the amount of current applied to the motor

during the kickstart time.

0 to 90/% locked rotor torque

u

If the controller senses that the motor has reached full speed before completing the Current

Limit Start, it will automatically switch to providing full voltage to the motor.