Control Terminal Designations

As shown in Figure 2.10, the SMC-Flex controller contains 24 control
terminals on the front of the controller.

Figure 2.10 – SMC-Flex Controller Control Terminals

Terminal

Number

Description

Terminal

Number

Description

11

Control Power Input

23

PTC Input

:

12

Control Power Common

24

PTC Input

:

13

Control Enable Input

:

25

Tach Input ( - )

14

Control Module Ground

26

Tach Input ( + )

15

Option Input #2

:

27

Ground Fault Transformer Input

:

16

Option Input #1

:

28

Ground Fault Transformer Input

:

17

Start Input

:

29

Fault Contact (N.O./N.C.) ➍

18

Stop Input

:

30

Fault Contact (N.O./N.C.) ➍

19

N.O. Aux. Contact #1 (Up-to-Speed)

; ➍

31

Alarm Contact (N.O./N.C.) ➍

20

N.O. Aux. Contact #1 (Up-to-Speed)

; ➍

32

Alarm Contact (N.O./N.C.) ➍

21

Not Used

33

Aux. Contact #2 (Normal) (N.O./N.C.) ➌ ➍

22

Not Used

34

Aux. Contact #2 (Normal) (N.O./N.C.) ➌ ➍

:

Do not connect any additional loads to these terminals. These “parasitic” loads may cause problems with operation,
which may result in false starting and stopping.

;

Aux. Contact #1 is always programmed for Up-to-Speed to control the bypass contactor in MV applications.

Aux. Contact #2 is always programmed for “Normal” indication in MV applications.

RC snubbers are required on inductive loads connected to auxiliary.

Note: The OFF state leakage current for a solid-state device connected to an SMC-Flex input must be less than 6 mA.