8ć10, Example of blockćtransfer ladder logic – Rockwell Automation 1785-LTx,D17856.2.1 Classic PLC-5 Programmable Controllers Users Manual User Manual

Page 105

Advertising
background image

Transferring Discrete and BlockĆTransfer Data

Chapter 8

8-10

Figure 8.5

Example Block Transfer from Supervisory Processor to a PLCĆ5/12,

Ć5/15, or Ć5/25 AdapterĆMode Processor to Local BlockĆTransfer Module

and Vice Versa

15553

BLOCK TRANSFER WRITE

Rack

Group

Module

Control

2

0

0=LOW

FB001:0000

Data File

Length

FB002:0000

0

BLOCK TRANSFER READ

Rack

Group

Module

Control

2

0

0=LOW

FB001:0000

Data File

Length

FB003:0000

0

BTR

BLOCK TRANSFER READ

Rack

Group

Module

Control Block

3

0

0

N7:10

Data File

Length

N7:100

40

Continuous

Y

BLOCK TRANSFER WRITE

Rack

Group

Module

Control Block

3

0

0

N7:20

Data File

Length

N7:150

8

BTW

Continuous

Y

BTW

BTR

Data File

FB002

0000

0039

Data File

FB003

0000

0007

Data File

N7

N7:100

N7:139

N7:150

N7:157

//

//

To BT

Module

From BT

Module

Supervisory Processor

in Supervisory Processor's

Remote I/O Rack 2

BT Module in Local

I/O Rack 0, I/O Group 2

Module 0

Block Transfers over Remote I/O Link

Local BT over chassis backplane

BLOCK TRANSFER WRITE

Rack

Group

Module

Control Block

0

2

0

N7:15

Data File

Length

N7:100

40

Continuous

Y

BTW

BLOCK TRANSFER READ

Rack

Group

Module

Control Block

0

2

0

N7:25

Data File

Length

N7:150

8

BTR

Continuous

Y

(PLCĆ3)

PLCĆ5/12, Ć5/15, or Ć5/25 AdapterĆMode Processor

If you block transfer data with a supervisory processor, you cannot use
1/2-slot addressing with a 1771-A4B chassis because the adapter-mode
processor needs the rack 3 I/O image table for block-transfer
communication. (This applies only to PLC-5/12, -5/15, and -5/25
processors in adapter mode.)

ATTENTION: Do not try block transfers to a supervisory
processor when the adapter-mode processor uses rack 3 for
scanning processor-resident local I/O (when you create your
own adapter image file using a PLC-5/12, -5/15, and -5/25
processor in adapter mode). Using rack 3 addresses under this
condition will result in unpredictable machine operation with
possible damage to equipment or personnel.

Example of BlockĆTransfer Ladder Logic

The following figures show example ladder logic for block transfers
between an adapter-mode processor and a supervisory processor.