Ać12 – Rockwell Automation 1785-LTx,D17856.2.1 Classic PLC-5 Programmable Controllers Users Manual User Manual

Page 150

Advertising
background image

Selecting Switch Settings

Appendix A

A-12

Set SW3 switch assembly switches to terminate either a DH+ link or a
remote I/O link. Switches 3 and 4 are unused.

1 2 3 4 5 6 7 8

1 2 3 4

Bottom View of Module

Switch Assembly SW3

toggle pushed
on (closed)

toggle pushed
off (open)

Side View

toward bottom

toward top

If the processor is:

Set switch:

To:

An end device on the remote I/O link

1

on

Not an end device on the remote I/O link

1

off

An end device on the DH+ link

2

on

Not an end device on the DH+ link

2

off

Switch 3 unused

3

off

Switch 4 unused

4

off

SW3