Transferring Discrete and BlockĆTransfer Data

Chapter 8

8-2

During each remote I/O scan:

the supervisory processor transfers 2, 4, 6 or 8 words—depending on

whether the adapter-mode processor is configured as a 1/4, 1/2, 3/4 or
full rack

the adapter-mode processor transfers 2, 4, 6 or 8 words—depending on

whether the adapter-mode processor is configured as a 1/4, 1/2, 3/4 or
full rack

Supervisory Processor in Scanner Mode

Remote I/O Scan

Write Outputs

Read Inputs

PLCĆ5 Processor in Adapter Mode

Read Inputs

Write Outputs

Program Scan

Immediate I/O

IIN (y)

ProcessorĆ

Rack

Data Exchange

I/O Image

Table

x

y

Resident

Housekeeping

Data

Exchange

IOT (x)

Buffer

Remote I/O

I/O Image

Table

Data Exchange

Logic

Scan

Figure 8.1 shows the transfers between supervisory processor output file
and adapter-mode processor input file as well as between adapter-mode
processor output file and supervisory processor input file.