A PLC-5 processor, in scanner mode, transfers discrete-transfer and
block-transfer data with processor-resident local and remote I/O chassis. If
you have your processor configured for scanner mode, refer to the
following sections for more information on how a PLC-5 processor
transfers data in scanner mode. Also, the following sections provide
information on how to handle I/O rack faults for processor-resident local
and remote I/O (in scanner mode).

The processor scans processor-resident local I/O synchronously and
sequentially to the program scan.

The processor:

scans discrete-transfer data in the processor-resident local I/O chassis

synchronously and sequentially to the program scan.

scans discrete-transfer data in remote I/O chassis asynchronously to the

program scan. The remote I/O scan discrete-transfers I/O data between
remote I/O adapters in I/O chassis and the remote I/O buffer in the
processor.

performs housekeeping once per program scan: 3 ms maximum;

typically 1.5 ms

Transferring Data

Using Scanner Mode

Programming Discrete

Transfer in Scanner Mode

Read Inputs

Write Inputs

ProcessorĆ

Rack

I/O Image

Table

Resident

Data

Exchange

Housekeeping

Logic

Scan

Program Scan