Calculating Program Timing

Chapter 9

9-4

I/O placed in the same chassis as the processor is called “processor-
resident” local I/O. These inputs and outputs are not updated during the
remote I/O scan—they are updated during the housekeeping portion of the
program scan. During housekeeping, the processor reads and writes the
I/O across the chassis backplane. Thus, the update of processor-resident
local I/O is synchronous to the program scan.

Figure 9.1 shows timing loops for discrete data transfer in a
PLC-5 processor.

Figure 9.1

Remote I/O Scan and Program Scan Timing Loops

Remote I/O

Buffer

x y

Adapter

Adapter

Adapter

Immediate I/O

IOT (x)

IIN (y)

ProcessorĆ

Rack

Data Exchange

I/O Image

Table

x

y

Resident

Data

Exchange

Rack 3

Rack 2

Rack 1

Remote I/O Scan

Program Scan

Timing Loop

Timing Loop

Read Inputs

Write Outputs

Housekeeping

Scan

Logic

During the housekeeping portion of the program scan, both the remote I/O
buffer and the processor-resident rack are updated. Remember that the I/O
scanner is constantly updating the remote I/O buffer asynchronously to the
program scan.