Selecting Switch Settings

Appendix A

A-2

Make the following switch selections for a 1771-AS, -ASB, or -ALX
adapter module.

Switch

Switch

5

6

1

2

ON

OFF

Last State

Switches

Processor Restart Lockout

Addressing

Outputs of this I/O chassis remain in their last state when a communication fault is

detected by this I/O adapter.

1

Outputs of this I/O chassis are turned off when a comunication fault is detected

by this I/O adapter.

Processor can restart the I/O chassis after a communication fault.

2

You must manually restart the I/O chassis with a switch wired to the

1771ĆAS or ĆASB.

ON

ON

ON

ON

ON

OFF

OFF

OFF
OFF

OFF

2Ćslot
1Ćslot

3

1/2Ćslot

3

Not allowed

Pressed in at top Closed (ON)

Pressed in at bottom Open (OFF)

Always

Off

Always

Off

19308

1. ATTENTION: If you set this switch to the ON position, when a communication fault is detected, outputs connected to

this chassis remain in their last state to allow machine motion to continue. We recommed that you set switch 1 to

the OFF position to deĆenergize outputs wired to this chassis when a fault is detected.

Also, if outputs are controlled by inputs in a different rack and a remote I/O rack fault occurs (in the inputs rack), the

inputs are left in their last nonĆfaulted state. The outputs may not be properly controlled and potential personnel

and machine damage may result. If you want your inputs to be anything other than their last nonĆfaulted state,

then you need to program a fault routine.

2. Set this switch to ON if you plan to use I/O rack autoĆconfiguration.

3. The 1771ĆASB series A adapter does not support 1/2Ćslot addressing.