Rockwell Automation 1785-LTx,D17856.2.1 Classic PLC-5 Programmable Controllers Users Manual User Manual

Page 144

Advertising
background image

Selecting Switch Settings

Appendix A

A-6

Select the switches to determine I/O rack, group, transmission rate, link
response, and scan for your adapter module using complementary I/O.

ONĊPrimary Chassis

OFFĊComplementary Chassis

1 2 3 4 5 6 7 8

O

N
O

F

F

SW

-

1

1 2 3 4

O

N
O

F

F

SW–2

5 6

Switch

1

2

ON
OFF
OFF
ON

OFF
OFF
ON
ON

57.6 KbpsĊ10,000 ft
115.2 KbpsĊ5,000 ft
230.4 KbpsĊ2,500 ft
not used

Maximum Chassis

Distance

ONĊscans for all but 4 last slots
OFFĊscans for all slots

OFFĊfor unrestricted

ONĊPrimary Chassis
OFFĊComplementary Chassis

I/O Rack Number

First I/O Group Number

Pressed in at top Closed (ON)

Pressed in at bottom Open (OFF)

Link Response: ONĊfor

series B emulation

I/O Rack Number

4

5

6

1

on

on

off

2

on

off

on

3

on

off

off

4

1

off

on

on

5

1

off

on

off

6

1

off

off

on

7

1

off

off

off

1

Valid for PLCĆ5/25 processors only. Only seven racks can be

complemented in a PLCĆ5 system.

For First I/O Group

Number

7

8

0

on

on

2

on

off

4

off

on

6

off

off

Remote I/O Adapter Module

1771ĆASB Series C with

Complementary I/O