Selecting Switch Settings

Appendix A

A-9

Set SW2 switch assembly switches for an adapter-mode PLC-5 processor
in a PLC-2/20 or -2/30 processor system or sub I/O scanner module
system. Set switches 2 through 8 for the number of words communicated
from host processor to adapter processor, for the I/O group, and for the
rack number of the I/O group of the adapter processor, respectively.
Switch 1 is unused.

1 2 3 4 5 6 7 8

1 2 3 4

Bottom View of Module

Switch Assembly SW2

Switch Assembly SW3

toggle pushed
on (closed)

toggle pushed
off (open)

Side View

toward bottom

toward top

If you want:

Set switch:

To:

Switch 1 is always unused.

1

off

The host processor to use 8 words to communicate with the adapter PLCĆ5

2

off

The host processor to use 4 words to communicate with the adapter PLCĆ5

2

on

First I/O group to be 0

3

on

First I/O group to be 4

3

off

Select the I/O rack number of the adapter PLCĆ5 processor

4 through 8

see below

Rack

4

5

6

7

8

01

on

on

on

on

on

02

on

on

on

on

off

03

on

on

on

off

on

04

on

on

on

off

off

05

on

on

off

on

on

06

on

on

off

on

off

07

on

on

off

off

on

AdapterĆMode

ProcessorsĊSW2 in a

PLCĆ2/20, Ć2/30, or Sub I/O

Scanner Module System