Choosing Hardware

Chapter 2

2-9

Choose from the following PLC-5 processors.

Table 2.I

Classic PLCĆ5 Processor Selection ChartĊPart 1

Processor/

Cat. No.

Maximum User

Memory Words

EEPROM Module

Memory (Words) &

Module Number

Total I/O Maximum

(any mix)

Analog

I/O Max

Program Scan Time /

K Word

I/O Scan time/Rack

(in a single Chassis,

extĆlocal or remote)

Multiple

MCPs /

Quantity

PLCĆ5/10

(1785ĆLT4)

6 K

8 K (1785ĆMJ)

512 (32ĆI/O modules)

256 (16ĆI/O modules)

128 (8ĆI/O modules)

256

2 ms (discrete logic)

8 ms (typical)

N/A

No / 1

PLCĆ5/12

(1785ĆLT3)

6 K

8 K (1785ĆMJ)

512 (32ĆI/O modules)

256 (16ĆI/O modules)

128 (8ĆI/O modules)

256

2 ms (discrete logic)

8 ms (typical)

10 ms @ 57.6 kbps

(remote)

No / 1

PLCĆ5/15

(1785ĆLT)

6 K expandable

to 10 K or 14 K

8 K (1785ĆMJ)

512 (any mix) or

512 in + 512 out

(complementary)

512

2 ms (discrete logic)

8 ms (typical)

10 ms @ 57.6 kbps

(remote)

No / 1

PLCĆ5/25

(1785ĆLT2)

13 K

expandable to

17 K or 21 K

8 K (1785ĆMJ) or

16 K (1785ĆMK)

1024 (any mix) or

1024 in + 1024 out

(complementary)

1024

2 ms (discrete logic)

8 ms (typical)

10 ms @ 57.6 kbps

(remote)

No / 1

Table 2.J

Classic PLCĆ5 Processor Selection ChartĊPart 2

Processor/

Number of Remote I/O Extended Local

Maximum

Number of

Maximum Number of I/O

Chassis

Number of

RSĆ232/

422/ 423

Remote I/O

Transmission

Backplane

Current

Processor/

Cat. No.

Number of Remote I/O, ExtendedĆLocal

I/O, and DH+ Ports

Number of

I/O Racks

Total

Ext Local

Remote

422/ 423

ports

Transmission

Rates

1

Current

Load

PLCĆ5/10

(1785ĆLT4)

1 DH+

1

1

0

0

0

ĆĆ

2.5A

PLCĆ5/12

(1785ĆLT3)

1 DH+

1 Remote I/O (Adapter Only)

4

1

0

0

0

57.6 kbps

2.5A

PLCĆ5/15

(1785ĆLT)

1 DH+

1 Remote I/O (Adapter or Scanner)

4

13

0

12

0

57.6 kbps

2.5A

PLCĆ5/25

(1785ĆLT2)

1 DH+

1 Remote I/O (Adapter or Scanner)

8

17

0

16

0

57.6 kbps

2.5A

Use the following steps as guidelines for selecting a power supply for a
chassis that contains a PLC-5 processor, a 1771-AS or -ASB remote I/O
adapter module, or a 1771-ALX extended-local I/O adapter module.

1.

Determine the input voltage for the power supply.

2.

Calculate the total backplane current draw for I/O modules by
adding together the backplane current draw for each I/O module in
that chassis.

Choosing a Classic PLCĆ5

Processor for Your

Application

Selecting Power Supplies

1771ĆP7