Maximizing System Performance

10-6

The processor time is the time needed to process the inputs and set the
corresponding outputs. This processor time varies for different processors
and is based on input buffering, program scan, etc.

In a PLC-5 system, both inputs and outputs are buffered between the I/O
image table and the I/O scanner. The movement of inputs from the scanner
to the input buffer is asynchronous to the movement of data from the input
buffer to the input image table. The worst-case processor time is:

Periodic input buffer update
One program scan to guarantee

inputs received

.18 ms times the number of racks

= 10 ms

= xx ms

= xx ms

One program scan to guarantee

outputs received

= xx ms

For a 3-rack system with a 20 ms program scan, the worst-case processor
time is: 10 + 20 + 20 + .54 = 50.54 ms.

To calculate throughput, use the following equation:

Input

Card

Delay

I/O Backplane

WorstĆCase

Remote I/O

Scan Time

WorstĆCase

Processor

Time

+

+

+

WorstĆCase

Remote I/O

Scan Time

+

I/O Backplane

+

Output

Card

Delay

+

An example of a worst-case update time calculation:

Input card delay

I/O backplane

WorstĆcase remote I/O scan time

WorstĆcase processor time

WorstĆcase remote I/O scan time

I/O backplane
Output card delay

= 20 ms (typical)

= 1 ms

= 30 ms

= 50.54 ms

= 30 ms

= 1 ms
= 8.8 ms (typical)

Total

141.34 ms