Selecting Switch Settings

Appendix A

A-11

Set SW2 switch assembly switches for an adapter-mode PLC-5 processor
in a PLC-3 or PLC-5/250 processor system. Set switch 2 for the number of
words communicated from the host processor to the adapter processor. Set
switch 3 for I/O group. Set switches 4 through 8 for the I/O rack number
of the adapter processor. Switch 1 is unused.

1 2 3 4 5 6 7 8

1 2 3 4

Bottom View of Module

Switch Assembly SW2

Switch Assembly SW3

toggle pushed
on (closed)

toggle pushed
off (open)

Side View

toward bottom

toward top

If you want:

Set switch:

To:

Switch 1 is always unused.

1

off

The host processor to use 4 words to communicate with the adapter PLCĆ5 processor

2

on

First I/O group to be 0

3

on

First I/O group to be 4

3

off

Select the I/O rack number of the adapter PLCĆ5 processor

4 through 8

see below

I/O Rack

Number

0

1

2

3

4

5

6

7

10

11

12

13

14

15

16

4

on

on

on

on

on

on

on

on

on

on

on

on

on

on

on

6

on

on

on

on

off

off

off

off

on

on

on

on

off

off

off

5

on

on

on

on

on

on

on

on

off

off

off

off

off

off

off

7

on

on

off

off

on

on

off

off

on

on

off

off

on

on

off

8

on

off

on

off

on

off

on

off

on

off

on

off

on

off

on

Switch

I/O Rack

Number

17

20

21

22

23

24

25

26

27

30

31

32

33

34

35

36

37

4

on

off

off

off

off

off

off

off

off

off

off

off

off

off

off

off

off

6

off

on

on

on

on

off

off

off

off

on

on

on

on

off

off

off

off

5

off

on

on

on

on

on

on

on

on

off

off

off

off

off

off

off

off

7

off

on

on

off

off

on

on

off

off

on

on

off

off

on

on

off

off

8

off

on

off

on

off

on

off

on

off

on

off

on

off

on

off

on

off

Switch

AdapterĆMode

ProcessorsĊSW2 in a

PLCĆ3 or PLCĆ5/250 System

with 4ĆWord Groups