Selecting Interrupt Routines

Chapter 7

7-4

Table 7.G

Response to Major Faults (Word 11 of the Status File)

This bit:

Indicates this fault:

And the fault is:

00

Corrupted program file

01

Corrupted address in ladder program (see fault codes 10Ć19)

02

Programming error (see fault codes 20Ć29)

RecoverableĊ

h f l i

05

StartĆup protection fault (see word 26, bit 1)

Processor sets bit 5; if your fault routine does not reset this bit,

the processor inhibits startup

the fault routine

can instruct the

processor to clear

the fault and then

07

UserĆgenerated fault; processor jumped to fault routine

(see fault codes 0Ć9)

the fault and then

resume scanning

the program.

08

Watchdog faulted

p g

13

STI file does not contain ladder logic or does not exist

03

Processor detected an SFC fault (see fault codes 74Ć79)

04

Processor detected an error when assembling a ladder

program file (see fault code 70)

Not recoverable

09

System is configured wrong; you installed a RAM cartridge but

configured the system for an EEPROM or you violated 32Ćpoint

I/O module placement rules for 1Ćslot addressing

Not recoverableĊ

the processor

enters fault mode

without scanning

10

NonĆrecoverable hardware error

without scanning

the fault routine.

14

Fault routine does not contain ladder logic or does not exist

15

Fault routine program file does not contain ladder logic

A remote block transfer from a fault routine causes the processor to stop
scanning all programs until the block transfer completes.

Major Fault Codes
Table 7.H lists major fault codes. The processor stores the fault code in
word 12 of the processor status file.