Transferring Discrete and BlockĆTransfer Data
Chapter 8
8-3
Figure 8.1
Automatic I/O Transfer between Supervisory and
AdapterĆMode Processors
15298
00
03
04
07
10
13
14
17
00
03
04
07
10
13
14
17
00
03
04
07
10
13
14
17
00
03
04
07
10
13
14
17
Word
0
1
2
3
4
5
6
7
Word
0
1
2
3
4
5
6
7
Supervisory Processor
AdapterĆMode Processor
I:30 - I:37 (or adapter image file)
Supervisory Processor
AdapterĆMode Processor
O:30 - O:37 (or adapter image file)
Supervisory Processor
PLCĆ2 0X0-0X7
PLCĆ3 OXX0-OXX7
PLCĆ5 O:X0-O:X7
Supervisory Processor
PLCĆ2 1X0-1X7
PLCĆ3 IXX0-IXX7
PLCĆ5 I:X0-I:X7
Output File
Input File
Input File
Output File
Word 0 is reserved for block transfer and status.
If data from the supervisory processor is intended to control outputs of the
adapter-mode processor, the ladder logic in the adapter-mode processor
must move the data from its input file (I/O rack 3 or the adapter image file)
to its output file (local I/O). Use XIC and OTE instructions for bit data;
use move and copy instructions for word data.
If you want the supervisory processor to read data from a data file in the
adapter-mode processor, ladder logic in the adapter-mode processor must
move that data to its output file (I/O rack 3 or the adapter image file) for
transfer to the supervisory processor.