Placing System Hardware

Chapter 3

3-3

(4")

Wiring Duct

Wiring Duct

(6")

1 8 7 4 9

Minimum spacing requirements for a remote

I/O chassis:

Mount the I/O chassis horizontally.

Allow 153 mm (6 in) above and below all

chassis. When you use more than one

chassis in the same area, allow 152.4 mm

(6 in) between each chassis.

Allow 102 mm (4 in) on the sides of each

chassis. When you use more than one

chassis in the same area, allow 101.6 mm

(4 in) between each chassis.

Allow 51 mm (2 in) vertically and

horizontally between any chassis and the

wiring duct or terminal strips.

Leave any excess space at the top of

the enclosure, where the temperature is

the highest.

Area reserved for disconnect.

transformer, control relays, mot or

starters or other user devices.

102mm

153mm

51mm (2")

51mm (2")

153mm (6")

(4")

102mm

(4")

102mm

153mm (6")