Placing System Hardware
Chapter 3
3-3
(4")
Wiring Duct
Wiring Duct
(6")
1 8 7 4 9
Minimum spacing requirements for a remote
I/O chassis:
•
Mount the I/O chassis horizontally.
•
Allow 153 mm (6 in) above and below all
chassis. When you use more than one
chassis in the same area, allow 152.4 mm
(6 in) between each chassis.
•
Allow 102 mm (4 in) on the sides of each
chassis. When you use more than one
chassis in the same area, allow 101.6 mm
(4 in) between each chassis.
•
Allow 51 mm (2 in) vertically and
horizontally between any chassis and the
wiring duct or terminal strips.
•
Leave any excess space at the top of
the enclosure, where the temperature is
the highest.
Area reserved for disconnect.
transformer, control relays, mot or
starters or other user devices.
102mm
153mm
51mm (2")
51mm (2")
153mm (6")
(4")
102mm
(4")
102mm
153mm (6")