Chapter

3

3-1

Placing System Hardware

A well-planned layout is essential to the proper installation of your Classic
PLC-5 programmable controller system. Read this chapter for information
on placing hardware.

If you want to read about:

Go to

page:

Proper environment

3Ć1

Protecting your system

3Ć4

Avoiding electrostatic damage

3Ć4

Planning your raceway layout

3Ć4

Planning your cabling

3Ć6

Grounding your system

3Ć7

Place the processor in an environment with conditions that fall within the
guidelines described in Table 3.A.

Table 3.A

Proper Environmental Conditions For Your Processor

Environmental Condition Acceptable Range
Operating temperature

0 to 60

°

C (32 to 140

°

F)

Storage temperature

Ć40 to 85

°

C (Ć40 to 185

°

F)

Relative humidity

5 to 95% (without condensation)

Separate your programmable controller system from other equipment and
plant walls to allow for convection cooling. Convection cooling draws a
vertical column of air upward over the processor. This cooling air must
not exceed 60

°

C (140

°

F) at any point immediately below the processor.

If the air temperature exceeds 60

°

C, install fans that bring in filtered air or

recirculate internal air inside the enclosure, or install air-conditioning/heat-
exchanger units.

Chapter Objectives

Determining the Proper

Environment

System Design

Determined

Choosing

Communication

Transferring Discrete

and Block Data

Planning Your

System Programs

Calculating Program

Timing

Assigning Addressing

Mode, Racks,

and Groups

Choosing Hardware

Placing System

Hardware

Selecting Interrupt

Routines