Rockwell Automation 1785-LTx,D17856.2.1 Classic PLC-5 Programmable Controllers Users Manual User Manual

Page 129

Advertising
background image

Calculating Program Timing

Chapter 9

9-12

Category

Words of

Memory

1

Time (

µ

s)

Integer or

Floating Point

False

Time (

µ

s)

Floating point

True

Time (

µ

s)

Integer

True

Title

Code

File

COP

copy

88 + 2.7W

104 + 3.8W

20

4Ć7

File

COP

copy

counter, timer, and control

88 + 2.7W

98 + 5.8W

104 + 3.8W

20

4 7

FLL

fill

81 + 2/.1 W

100 + 3.1W

15

counter, timer, and control 97 + 4.4W

Shift Register

BSL

bit shift left

74 + 3.4W

57

BSR

bit shift right

78 + 3.0W

FFL

FIFO load

54

44

FFU

FIFO unload

68 + 3.2W

46

Diagnostic

FBC

file bit compare

6Ć11

0 mismatch

75 + 6W

31

1 mismatch

130 + 6W

2 mismatches

151 + 6W

DDT

diagnostic detect
0 mismatch

71 + 6W

31

1 mismatch

150 + 6W

2 mismatches

161 + 6W

Zone Control

MCR

master control

12

18

1

Immediate I/O

IIN

immediate input

2Ć3

local

196

16

remote

204

IOT

immediate output
local

202

16

remote

166

Sequencer

SQI

sequencer input

57

14

5Ć9

SQL

sequencer load

55

42

4Ć7

SQO

sequencer output

77

42

5Ć9

Jump and Subroutine

JMP

jump

45

15

2Ć3

JSR

jump to subroutine

SBR

0 parameters

56

15

2Ć3

1 parameter

91

3Ć5

add per parameter

21

RET

return from sub.
0 parameters

48

13

1

1 parameter

70

2Ć3

add per parameter

21

LBL

label

12

12

3

W = number of elements acted on per scan

1

Use the smaller number if all addresses are below word 4096; use the larger number if all addresses are above 4096.

Advertising