Rockwell Automation 1785-LTx,D17856.2.1 Classic PLC-5 Programmable Controllers Users Manual User Manual

Page 31

Advertising
background image

Choosing Hardware

Chapter 2

2-12

Powering a Remote I/O Chassis Containing a 1771ĆAS or 1771ĆASB or

an ExtendedĆLocal I/O Chassis Containing a 1771ĆALX

Table 2.L lists the power supply modules that you can use with a remote
I/O chassis or an extended-local I/O chassis.

Table 2.L

Powering a Remote I/O Chassis (Containing a 1771ĆAS or ĆASB)

or an ExtendedĆLocal I/O Chassis (Containing a 1771ĆALX)

Power

Input

Output Current Output Current (in Amps) When Parallel with:

Power Supply

Power

Supply

Input

Power

Output Current

(in Amps)

P3

P4

P4S

P4S1 P5

P6S

P6S1

Power Supply

Location

1771ĆP3

120V ac

3

6

11

11

chassis, 1Ćslot

1771ĆP4

120V ac

8

11

16

16

chassis, 2Ćslot

1771ĆP4S

120V ac

8

11

16

16

chassis, 1Ćslot

1771ĆP4S1 100V ac

8

16

1771ĆP4R

120V ac

8/16/24

1

1771ĆP5

24V dc

8

16

chassis, 2Ćslot

1771ĆP6S

220V ac

8

16

chassis, 1Ćslot

1771ĆP6S1 200V ac

8

16

1771ĆP6R

220V ac

8/16/24

1

1771ĆP1

120/220V ac

6.5

external

2

1771ĆP2

120/220V ac

6.5

1771ĆP7

120/220V ac

16

1771ĆPS7

120/220V ac

16

1777ĆP2

120/220V ac

9

1777ĆP4

24V dc

9

1

See publication 1771Ć2.136 for more information.

2

You cannot use an external power supply and a slotĆbased power supply module to power the same chassis;
they are not compatible.

Advertising