Assigning Addressing Modes,

Racks, and Groups

Chapter 4

4-6

Using 1ĆSlot Addressing

When you select 1-slot addressing, the processor addresses one I/O
module slot as one I/O group. Each physical slot in the chassis
corresponds to an input and output image-table word. The type
(unidirectional or bidirectional) and density of module that you install
determines the number of bits used in these words.

8-Point I/O Modules
You can place any mix of 8- or 16-point I/O modules
(including bidirectional modules such as
block-transfer modules) in any order with 1-slot
addressing. The 8- or 16-point modules do not
interfere with the I/O image of the other 8- or
16-point modules.

16-Point I/O Modules
A single 16-point module uses an entire word of the
processor image table.

Block-Transfer Module Addressing
To address a single-slot block transfer module in a
1-slot I/O group, use the assigned I/O rack and group
numbers of the slot (in which the module resides) and
0 for the module number. To address a double-slot
block-transfer module, use the assigned I/O rack
number, the lower assigned I/O group number, and 0
for the module number.

0

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

17 16 15 14

12

10 07 06 05

03 02 01 00

04

11

13

17 16 15 14

12

10 07 06 05

03 02 01 00

04

11

13

o r

11869

1ĆSlot I/O Group with One 16Ćpt Digital Discrete

I/O Module

A single 16Ćpt module uses an entire word of image table.

1-Slot

I/O Group

Output ImageĆTable Word Corresponding to the I/O Group.

Input ImageĆTable Word Corresponding to the I/O Group.

1-Slot

I/O Group

Input

Terminals

Output

Terminals