Selecting Switch Settings

Appendix A

A-4

Select the switches to determine I/O rack, group, transmission rate, link
response, and scan for your adapter module without complementary I/O.

1 2 3 4

O

N
O

F

F

SW–2

1 2 3 4 5 6 7 8

O

N
O

F

F

SW–1

5 6

Switch

1

2

ON
OFF
OFF
ON

OFF
OFF
ON
ON

57.6 KbpsĊ10,000 ft

115.2 KbpsĊ5,000 ft
230.4 KbpsĊ2,500 ft
Not used

Maximum Chassis

Distance

Pressed in at top Closed (ON)

Pressed in at bottom Open (OFF)

I/O Rack Number

(see next page)

First I/O Group Number

(see below)

Link Response: ONĊfor series B emulation

OFFĊfor

unrestricted

Scan: ONĊfor all but last 4 slots

OFFĊfor all slots

on = closed

off = open

First I/O Group

Number

7

8

0

on

on

2

on

off

4

off

on

6

off

off

Remote I/O Adapter Module

1771ĆASB Series C without

Complementary I/O