Planning Your System Programs
Chapter 6
6-10
Table 6.F
Processor Status File Addresses
This word of the status file:
Stores:
S:0
Arithmetic flags
•
bit 0= carry
•
bit 1 = overflow
•
bit 2= zero
•
bit 3 = sign
S:1
Processor status and flags
S:2
Switch settings:
•
bits 0 Ć 5 = DH+ station #
•
bit 7 = set is scanner; reset is adapter (PLCĆ5/15, Ć5/25 only)
•
bit 11, 12 = HW addressing
bit 12
bit 11
0
0
illegal
1
0
1/2Ćslot
0
1
1Ćslot
1
1
2Ćslot
•
bit 13, 14 = EEPROM
bit 13
bit 14
0
0
EEPROM transfer if processor memory bad
0
1
EEPROM transfer disabled
1
1
EEPROM transfer at powerĆup
•
bit 15 = set is memory unprotected
S:3 to S:6
Active Node table:
Word
Bits
DH+ Station #
3
0Ć15
00Ć17
4
0Ć15
20Ć37
5
0Ć15
40Ć57
6
0Ć15
60Ć77
S:8
Last program scan duration (in ms)
S:9
Maximum program scan duration (in ms)
S:10
Minor fault bits
S:11
Major fault bits
S:12
Fault code storage location
S:13
Program file where fault occurred
S:14
Rung number where fault occurred
S:16
I/O status file number storage location
S:18
Processor clock year
S:19
Processor clock month
S:20
Processor clock day
S:21
Processor clock hour
S:22
Processor clock minute
S:23
Processor clock second
S:24
Indexed addressing offset
S:25
(PLCĆ5/12, Ć5/15, Ć5/25 only)
I/O adapter image file
S:26
User control bits for processor startĆup routine