Rockwell Automation 1785-LTx,D17856.2.1 Classic PLC-5 Programmable Controllers Users Manual User Manual

Page 52

Advertising
background image

Assigning Addressing Modes,

Racks, and Groups

Chapter 4

4-10

When assigning rack numbers, use the following guidelines:

One I/O rack number is eight I/O groups, regardless of the addressing

mode that you select.

You can assign from one to four racks in your processor-resident

local chassis (128 inputs and 128 outputs) depending on the chassis
size and addressing mode. You cannot split a processor-resident local
I/O rack over two or more chassis or assign unused processor-resident
local I/O groups to remote I/O racks.

The default address of the processor-resident local rack is 0. You can

change the default to 1 by setting bit 2 in the processor control word
(S:26) on the processor configuration screen; you must also change the
mode of the processor from run to program to run.

An extended-local I/O and a remote I/O chassis cannot be addressed by

the same I/O rack number. For example, if an 8-slot extended-local I/O
chassis is configured as I/O groups 0-3 of I/O rack 2, an 8-slot remote
I/O chassis cannot be configured as I/O groups 4-7 of I/O rack 2.

Remote I/O Racks

You can assign a remote I/O rack to a fraction of a chassis, a single I/O
chassis, or multiple I/O chassis:

I/O Rack No.0 I/O Rack No.1

01 23 45 67 01 23 45 67

0 1 2 3 4 5 6 7

I/O Rack No.2

0 1 2 3

4 5

6 7

I/O Rack No.3

16466

16Ćslot chassis, two racks

Power source not indicated

Power source not indicated

One

16Ćslot chassis, one rack

One

4Ćslot chassis, 1/2 rack

Power source not indicated

One

2Ćslot chassis, 1/4 rack each

Power source not indicated

Two