When assigning remote I/O rack numbers, use the following guidelines:

Limit the number of remote I/O rack numbers to those that your PLC-5

processor can support.

The PLC-5 processor and the 1771-ASB adapter module automatically

allocate the next higher rack number(s) to the remaining I/O groups of
the chassis. For example, if you select 1/2-slot addressing for your
processor-resident local chassis and you are using a 16-slot (1771-A4B)
chassis, the processor will address racks 0, 1, 2, and 3 in this chassis.

BlockĆTransfer Module Racks Using 1/2ĆSlot Addressing

To address a block-transfer module in a 1/2-slot I/O group, use the
assigned rack number, the lower assigned I/O group number of the slot(s)
in which the module resides, and 0 for the module number (Figure 4.4).

Figure 4.4

Example BlockĆTransfer Module Address Using 1/2ĆSlot Addressing

0–3

4–7

0–3

4–7

0–3

4–7

0–3

4–7

This example is valid for a singleĆslot

BT module only.

I/O Group

Number

Rack 0

Rack 1

Rack 2

Rack 3

Rack = 2

Group = 4

Slot = 0