Rockwell Automation 1747-SDN SLC 500 DeviceNet Scanner Module User Manual User Manual

Page 101

Advertising
background image

Publication 1747-UM655B-EN-P - June 2007

DeviceNet Explicit Messaging 101

Control Block Layout

The control block layout is shown below.

SLC 5/0x DeviceNet Explicit Message (DEM) Control Block Structure

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

0

Word 0

EN

DN

ER

WS

AB

Error Code

Word 1

IMR

Message Timeout Preset

Word 2

Message Timeout Accumulator

Word 3

Message Timer Scaled Zero

Word 4

Unused

Word 5

Unused

Word 6

Transaction ID

Scanner Command

Word 7

Scanner Port (always 0x00)

Size of Send Data (in bytes)

Word 8

Service Code

Target MAC ID

Word 9

Reserved (not transmitted)

Class

Word 10

Instance

Word 11

Reserved (not transmitted)

Attribute (optional)

Word 12

Transaction Send Data

(next 26 words)

Word 37

Word 38

Transaction ID

Scanner Status

Word 39

Scanner Port (always 0x00)

Size of Reply Data (in bytes)

Word 40

Reply Service Code

Target MAC ID

Word 41

Transaction Reply/Receive Data

(next 29 words)

Word 69