DeviceNet Explicit Messaging 101
Control Block Layout
The control block layout is shown below.
SLC 5/0x DeviceNet Explicit Message (DEM) Control Block Structure
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
0
Word 0
EN
DN
ER
WS
AB
Error Code
Word 1
IMR
Message Timeout Preset
Word 2
Message Timeout Accumulator
Word 3
Message Timer Scaled Zero
Word 4
Unused
Word 5
Unused
Word 6
Transaction ID
Scanner Command
Word 7
Scanner Port (always 0x00)
Size of Send Data (in bytes)
Word 8
Service Code
Target MAC ID
Word 9
Reserved (not transmitted)
Class
Word 10
Instance
Word 11
Reserved (not transmitted)
Attribute (optional)
Word 12
Transaction Send Data
(next 26 words)
…
Word 37
Word 38
Transaction ID
Scanner Status
Word 39
Scanner Port (always 0x00)
Size of Reply Data (in bytes)
Word 40
Reply Service Code
Target MAC ID
Word 41
Transaction Reply/Receive Data
(next 29 words)
…
Word 69