Hardware Setup 37

Bank S1 DIP Switches

Switch

Setting

Position

Switches
1…3

Upper digit
of DF1
station
address

SW1

SW2

SW3

Digit

ON

ON

ON

0

Switches
4…6

Lower digit
of DF1
station
address

SW4

SW5

SW6

Digit

ON

ON

ON

0

Switches 7…8

Both OFF

Bank S2 DIP Switches

Switch

Setting

Position

Switches
1…3

Upper digit
of DF1
station
address

SW1

SW2

SW3

Digit

ON

OFF

OFF

19200

Switch 4

Full/Half-dup
lex

OFF = Full-duplex

Switch 5

Parity

OFF = No parity

Switch 6

Odd/even
parity

Not applicable

Switch 7

Handshake

OFF = Hardware handshake disabled

Switch 8

Diagnostic
command
execution

OFF = Disabled

Bank S3 DIP Switches

Switch

Setting

Position

Switch 1

Duplicate
detect

ON = Duplicate detect on

Switch 2

Error
detect

OFF = CRC error check

Switches
3…4

Number of
retries

SW3

SW4

Number of retries

ON

ON

0

Switches
5…8

DF1 ACK
time-out

SW5

SW6

SW7

SW8

Time Out

OFF

OFF

OFF

OFF

3.2