Publication 1747-UM655B-EN-P - June 2007

84 Creating and Running the Example Application Program

Download and Run the Program via an Ethernet Network

Follow the procedure below to download and run the example
program via an Ethernet network.

1. From the RSLogix 500 Communication menu, choose System

Comms.

The Communication dialog opens. Your dialog may look
different depending upon the drivers you have installed.

2. Click the + next to your Ethernet driver (AB-ETH-1 above) to

expand the tree.

3. Select the SLC 500 processor as shown above and click

Download.

4. Put the processor in Run mode after the download is complete.

IMPORTANT

To communicate with your SLC 5/05 processor over an Ethernet
network you must first configure the processor’s Ethernet
communication channel and assign it a unique IP address.

See Appendix B for information on configuring the Ethernet
communication channel.

IMPORTANT

You must also place the 1747-SDN module in Run mode by
setting the Run Bit (bit 0) in the scanner’s command register.
The command register is located at word 0 in the Output image
table.