Publication 1747-UM655B-EN-P - June 2007

Configuring the DeviceNet Network 53

If 00 appears to the right of the 1747-SDN icon and you do not need
to change the node address or baud rate of any device, skip the
remainder of this section and go to Configure the I/O Devices on
page 55.

Follow these steps to set the node address.

1. From the Tools menu, choose Node Commissioning.

The Node Commissioning dialog appears.

2. Click Browse.

The Device Selection dialog appears.

IMPORTANT

The network must not be active when performing node
commissioning on the 1747-SDN module. Make sure the
processor is in Program mode.

(Note that this applies only to the 1747-SDN module. You may
commission other devices with the processor in Run mode.)